Power Supply | |
24 VDC/48 VDC/110 VDC/220 VAC | Nominal Supply Voltage |
20% | Range of Changes |
2W | Input Power |
Current Input | |
0~1A – 0~5A | Nominal Current Input |
1~9999 (max. CT primary 50kA/5A 10kA/1A) | External CT Ratio |
Voltage Input | |
0~400V | Nominal Input Voltage |
80~500V | Three – Phase Line |
50~290V | Single – Phase |
1~10 (max. PT primary 1200V) | External PT Ratio |
Protocol Support | |
MODBUS / DNP3 | Slave |
Digital I/O | |
x8 Digital Input | Digital Input |
x4 Relay Output or x3 Relay Output & x1 Pulse Output or x8 Relay Output | Digital Output |
Parameter Measurement | |
√ | Voltage True RMS |
√ | Input Current True RMS |
√ | Line to Ground Fault |
√ | Line to Line Fault |
√ | Over Voltage |
√ | Over Current |
√ | Active Power |
√ | Reactive Power |
√ | Apparent Power |
√ | Power Factor |
√ | Frequency |
√ | Voltage THD |
√ | Current THD |
√ | Demand |
√ | Energy |
√ | Cos ɸ |
Casing | |
96x96x89 mm (W x H x D) | Dimension |
Accuracy | |
IEC 62053-21, IEC 62053-22, IEC 62053-23, EN 50470-1, EN 50470-3, ANSI C12.20, and IEEE1459 standards, IEC 61000-4-7 Class I and Class II | Supports |