WL

12÷36kV:
The WL series of medium voltage vacuum circuit breakers for indoor installation are realized using the separate pole technique.
Each pole has a vacuum interrupter inside which, thanks to a special production process, is built in the resin directly during the cylinder moulding stage.
This construction technique ensure protection of the vacuum interrupter against impact, dust and condensation.
Remote control is possible thanks to special electrical accessories (geared motor, shunt opening release, etc.).
The operating mechanism, the three poles and the current sensors (if provided) are mounted on a metallic frame without wheels.
The device is particularly compact, sturdy and with very low weight.

Main electrical characteristics
Rated voltage

kV

12

24

36

Rated power-frequency withstand voltage 50Hz 1min

kV (r.m.s.)

28

50

70

Rated lightning impulse withstand voltage

kV (peak)

75

125

170

Rated frequency

Hz

50-60

Rated current

A

630
1250

630

Breaking capacity

kA

16
20

16

20

Rated short-circuit current

kA

16 - 3s
20 -3s

16 - 3s 20 - 3s

Peak value

kA

40
50

40

50